Contributors: Brian Bates, Raymond Smith, Duane Waite

The storm is only the first problem

The hurricane has passed. The roof held, the windows held, and the generators started as designed. Then one utility failure triggers the next: city water stops, the chillers lose makeup water, a sealed hospital in August starts getting hotter by the hour, flooded roads block the scheduled fuel delivery, and the toilets stop flushing.

Nothing in that building failed code. The building survived the storm, but the systems it depends on did not—and without them, it cannot keep doing its job. That is the gap coastal resilience planning has to close.

Survivable isn’t the same as occupiable

While commercial buildings typically plan to be evacuated, critical facilities like hospitals, data centers, and emergency operations centers are expected to keep working when the community needs them most. Designing these facilities to operate in island mode—independently of the electrical grid—allows them to maintain essential services during outages while supporting the broader community’s response and recovery.

So coastal resilience means designing for the period after the storm, not just for the storm itself. The question isn’t only whether the building stays standing. It’s whether the building can keep doing its job for days, with no outside help, no deliveries, and no staff coming in for the next shift.

Answering that changes what is planned. And surprisingly, the failures that end operations are usually small:

  • A fuel pump below flood level.
  • Fuel stored on site with no way to move it to the generator that needs it.
  • A cooling tower with no makeup water.
  • Toilets that can’t flush.

The Hurricane Katrina response at Memorial Medical Center in New Orleans is a familiar example. Floodwater reached the lower levels of the hospital, where emergency power equipment was located. When power failed, the cooling, ventilators, and elevators failed with it. A facility can spend heavily on hardening and still be stopped by its weakest link.

Every system depends on another

Coastal risk is compound risk. One event sets off several failures, and the building’s systems are tied together in ways that are easy to miss until something breaks. Designing for it means tracing each critical function through the full chain it depends on: the equipment, the power and water it needs, the fuel or supplies that sustain it, the people who operate it and the access routes that allow support to reach the site.

Take a common request: keep the whole building fully conditioned during an outage. That’s reasonable, but it means a bigger generator, which burns more fuel, which needs more storage or a more reliable resupply plan. Each comfort or continuity choice adds load to the backup systems.

Water and sanitation are the dependencies most often underestimated. Once people are sheltering in a building and the toilets stop flushing, sanitation becomes the most urgent problem in the building. Facilities that plan to keep staff on site for days also need water and food stored on site and space where people can sleep.

Each building type has a different goal, and the plan should reflect it:

  • Hospitals keep patients in place. Moving someone from the ICU can be riskier than staying in place.
  • Commercial buildings usually aim to get most people out, then keep the people who stay safe and reasonably comfortable.
  • Data centers have few people to protect. The priority is removing heat and keeping equipment running so communications stay online.
  • Emergency operations centers and 911 call centers are where the response is run. Staff may stay for days, so the building has to keep communications up and support people living and working on site.
  • Airports need to reopen quickly once the storm passes. Power, fuel, and access have to be restored fast enough for relief flights and supplies to get in.

The core concerns for resilience are mostly the same: fuel, water, temperature control, sanitation, and staff who can’t get to the site.

Coastal conditions add their own costs

Coastal conditions vary across North America, and the added costs vary with them. Gulf and Atlantic coast projects may need to account for hurricanes, storm surge and high groundwater. Pacific coast facilities face seismic risk alongside salt exposure, while northern coastlines and the Great Lakes add freeze-thaw cycles, ice and severe winter weather. Local soils, flood elevations, wind speeds and code requirements can significantly change the design—and the budget—even for otherwise similar facilities.

Charleston shows how these regional conditions can overlap. In addition to flood exposure, the city is in Seismic Design Category D because of the 1886 earthquake, has poor soils and has design wind speeds of more than 150 mph. Critical facilities there are often classified as Risk Category IV, the code category for essential facilities such as hospitals with emergency treatment. Together, these conditions raise structural, envelope and anchorage requirements—and can make budgets based on inland projects significantly underestimate the cost.

A painted NEMA 3R enclosure should last 20-30 years, and a NEMA 4X stainless steel enclosure should last 50+ years. In coastal areas, these life spans can be significantly reduced.

Salt air works more slowly but steadily. Equipment and enclosures expected to last decades can wear out much sooner on the coast, and even stainless steel can corrode early. That affects equipment selection from the start:

  • Corrosion-resistant coatings on coils.
  • Copper fins in place of standard aluminum.
  • Enclosures chosen for their lifecycle cost on the coast, not just their first cost.

Coastal areas also see more lightning, so power quality is less reliable than inland. MRI machines, imaging systems, and data center equipment are sensitive to the dips and spikes. Lightning protection is standard for critical buildings. Power conditioning, UPS systems, and surge protection deserve the same attention.

How to get from survivable to operable

Code tells a design team how strong the building has to be. It doesn’t say what the building has to keep doing after the storm, or for how long. Those answers have to come from the owner.

Designing critical facilities to remain operational during emergencies requires two complementary strategies: redundancy and resilience.

  • Redundancy involves intentionally duplicating essential systems, equipment, or infrastructure so operations can continue if a primary component fails.
  • Resilience is a facility’s ability to anticipate, absorb, adapt to, and recover quickly from disruptions while maintaining essential operations.

Together, redundancy and resilience provide the foundation for facilities that can continue serving their communities under challenging conditions.

A comprehensive risk assessment helps translate these principles into practical design decisions. This process requires input from stakeholders across the facility, not just the engineering team. For hospitals, that means considering patient care requirements, critical medical equipment, infection prevention and control, life safety systems, and the operational capabilities of facility personnel. For data centers, considerations include maintaining power and cooling, protecting critical IT infrastructure, and supporting uninterrupted operations. For airports, priorities may include maintaining airfield operations, communications, security systems, and passenger safety during disruptions. Each facility has different operational priorities, making stakeholder involvement essential to developing resilience strategies that work in practice.

Staffing is an especially important consideration. During and after a major disruption, employees may be unable to reach the facility, leaving smaller teams responsible for maintaining essential operations. Understanding these operational realities early in the design process helps engineers develop solutions that support both the facility’s technical systems and the people who depend on them.

Five practical steps to build coastal resilience

Building resilience into critical facilities requires more than protecting infrastructure from extreme weather. It means understanding how a facility must function during a disruption, identifying where systems and operations are most vulnerable, and making informed decisions about where to invest. These five steps can help facility leaders and their design teams translate resilience goals into practical strategies.

1. Start with a shared risk assessment. This can’t be done by engineers alone. The strongest assessments bring together:

  • Administrators, facility and environmental services staff.
  • Architects and engineers.
  • First responders in the community

They work through what could go wrong and how the facility would respond. The results shape design decisions:

  • How much water, food, and fuel storage is needed.
  • Which services go on which floors.
  • How emergency teams reach the site.

2. Decide how long the building has to run on its own. Federal and state agencies have rules that give a baseline for hospitals—usually 96 hours or longer. CMS and The Joint Commission require a plan to show how you continue to operate. The requirement can be met with a mix of on-site supply, resupply agreements and reduced operations. Some organizations will want to go further to keep caring for the community after an event. The answer should come from the facility’s mission, not a default number.

3. Accept the trade-offs. Not every risk can be eliminated. Fuel, water and supply storage gets expensive quickly and takes up space. Past a certain point, each added hour of independence costs more and helps less, especially when the surrounding community is no longer functioning anyway. That trade-off should be discussed openly, not avoided.

4. Weigh one investment against another. With a limited budget, the question is where each dollar lowers risk the most. Full N+1 redundancy for HVAC equipment may matter less than more fuel storage, or the reverse. Redundancy can often be built into a single unit, which costs less than adding a second complete unit.

5. Plan for how the building is actually operated. Small design details decide whether a plan works under stress:

  • A fuel transfer system so no one has to pump between tanks by hand.
  • Interior access to equipment that may need service during a storm, so no one has to go on the roof in hurricane-force wind.
  • Spaces that can be turned into staff sleeping quarters.

Build resilience into investments you’re already making

Most facilities can’t fund a full resilience retrofit. Few have to. The most practical approach is to use replacements that are already in the capital plan.

When equipment reaches end of life, treat the replacement as a chance to upgrade, not a like-for-like swap. The added cost is usually small compared with the cost of the project. Examples:

  • HVAC fans: replace a single fan with a fan wall, so the unit keeps running if one fan fails.
  • Large single units: replace one large unit with three smaller ones, where any two can carry the load. That builds in N+1 redundancy.
  • Generators: when a generator is replaced, increase fuel storage or improve the transfer system at the same time.
  • Piping and conduit: raise them above flood level when they’re being rerouted.
  • Materials: choose coatings and materials built for salt air.

Spread over several capital cycles, these upgrades turn a building that can survive a storm into one that can keep operating.

How Salas O’Brien can help

You’re making these decisions with limited capital, aging buildings, and a mission that has to continue when the community depends on it most. You don’t need every risk eliminated. You need clear priorities and a plan that holds up in real conditions.

Our engineers have spent decades designing critical facilities in coastal environments, from Gulf Coast commercial buildings to Southeast hospitals and emergency operations centers to West Coast seismic resilience. We know where the weak links usually are:

  • Fuel delivery
  • Makeup water
  • Sanitation
  • Corrosion
  • Power quality

We bring that experience to a risk assessment you develop together with your administrators, operators, and clinical staff.

From there, we help you weigh the trade-offs, set a realistic target for how long the facility can run on its own, and build resilience into the capital plan you already have. That can be a new essential facility or the next equipment replacement. Our cross-sector work in healthcare, data centers, aviation, government, and commercial facilities means we understand how each building’s goal shapes the right answer.

Reach out to discuss your project with one of our experts below.

For media inquiries on this article, reach out to [email protected].

Contributors
Brian Bates, PE, RCDD

Brian Bates, PE, RCDD

Brian Bates designs electrical power and life safety systems for hospitals and other critical facilities on the Southeast coast. He helps healthcare clients with defend-in-place planning and risk assessments that keep buildings running through hurricanes, flooding and long utility outages. His work addresses the conditions coastal facilities face: salt air corrosion, lightning-related power disturbances and the combined seismic and wind demands of the Charleston area. Brian serves as a Principal for Salas O’Brien. Contact him at [email protected]

All Posts

Raymond Smith, PE

Raymond Smith, PE

Raymond Smith, PE brings more than 20 years of engineering experience in challenging coastal environments. He combines technical expertise with strategic leadership to deliver practical, resilient solutions tailored to client needs. His approach emphasizes collaboration, successful project outcomes, and long-term client relationships. Raymond serves as the Director of Mechanical and Plumbing Design. Contact him at [email protected].

All Posts

Duane Waite

Duane Waite

Duane Waite, with 39 years of experience managing electrical engineering teams, combines a hands-on approach with an eye for detail, inspiring his team to deliver quality work consistently. His commitment to continuing education and mentorship, combined with reliable, efficient communication and information-tracking systems, has proven highly advantageous on complex projects such as hospitals, pharmaceutical, educational, governmental, and industrial facilities. Duane serves as a Principal at Salas O’Brien and Head of the Electrical Department in Canada. Contact him at [email protected].